BTD   

Effective pressure transducer for clean air


Effective pressure transducer based on the dynamic measurement principle for volume flow rate measuring units VME and VMR

 

  • Use in ventilation and air conditioning systems, only with clean air
  • Analogue or digital actual value signal for monitoring and evaluation by the central BMS
  • Suitable for constant and variable volume flows
  • No commissioning required as parameters are factory set 
  • Recording of measured values for the display of volume flow rates or for the control of slave controllers
  • Service access for PC configuration software
  • Access with a smartphone thanks to NFC interface and BlueCON
  • Data transparency due to bus communication with MP bus, Modbus RTU or BACnet MS/TP

Product successfully added to cart

General information

Application

  • Determination of volume flow rates and transmission/processing as an electrical signal for monitoring/tracking control
  • Measurement of an effective pressure and conversion of the volume flow rate actual value into an analogue and digital actual value signal 
  • For use only with clean air
  • Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection
  • Volume flow rate actual value is available as a network data point or linear voltage signal
  • Use TROX FlowCheck app and PC tool to configure the controller and the communication parameters
  • Transducer factory-set to the unit-related constant (K value) of the measuring unit

 

With heavy dust levels in the room

  • Install appropriate exhaust air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement.

 

If the air is additionally contaminated, e.g. with fluff or sticky components

  • Use of the BTS attachment group instead of the BTD universal controller described here 


Interface


Analogue interface

  • Analogue interface with adjustable signal voltage range

 

Digital communication interface (bus)

  • MP bus
  • Modbus RTU, RS485
  • BACnet MS/TP, RS485
  • Data points, see bus lists

 

Factory setting

  • Actual value output via analogue interface and Modbus communication interface

Signal voltage ranges

  • 0 – 10 V DC
  • 2 – 10 V DC

Parts and characteristics

  • Effective pressure transducer according to the dynamic measurement principle (dynamic transducer)
  • Plug-in terminals for supply line and controls including cover
  • NFC and service interface
  • Indicator lights for displaying the operating mode
  • Controller casing prepared with 4 openings for threaded connections, 2 cable glands M16 x 1.5 for connecting cable in the supply package

Construction

Type VRU-D3-M/B TR for volume flow rate measuring unit

  • For VME all dimensions
  • For VMR all dimensions

Commissioning


  • All parameters are factory-set
  • On-site adjusting is not required
  • Modbus/BACnet/MP bus interface: additional commissioning steps may be required
  • Operating parameters can be adjusted using the TROX FlowCheck app

Useful additions

TROX FlowCheck app for Android and iOS

  • Belimo PC-Tool
  • BlueCON-to-NFC converter ZIP-BT-NFC

Specification text

Category

  • Volume flow rate measuring unit


Application

  • Recording of a constant or variable volume flow rate actual value, e.g. for connection to the central building management system for the purpose of monitoring or integration into a room balancing system


Pressure range

  • Effective pressure transducer for dynamic pressure measurements in ventilation and air conditioning systems with clean air


Installation orientation

  • Either direction


Connection

  • Plug-in terminals with cover. No connection box required


Supply voltage

  • 24 V AC/DC


Interface/Control

Analogue signal

  • 0 – 10 V DC; 2 – 10 V DC


or digital bus connection

  • Modbus RTU
  • BACnet MS/TP
  • MP bus


Interface type can be set and connected by others


Interface information

Analogue signal:

  • Volume flow rate actual value


Bus interface:

  • Volume flow rate actual value
  • Error status


System connections

  • Flexible integration into digital bus systems


Parameter setting

  • Parameters specific to measuring unit are factory-set
  • Signal characteristic factory set


Subsequent adjustment using optional tools: 

  • TROX FlowCheck app, PC software (wired)


Condition upon delivery

  • Electronic transducer is factory mounted on the measuring unit
  • Factory-set parameters
  • Functional test with air (see sticker)

Technische informatie

Function, Order code

  • FUNCTION
  • ODER CODE
Principle of operation – volume flow rate measuring unit Funktionsprinzip_XTDai.png

① Effective pressure transducer (dynamic measurement principle)

② Transducer for converting the differential pressure signal into a volume flow rate signal

③ Analogue actual value signal


The volume flow rate measurement is carried out by measuring an effective pressure. The volume flow rate measuring unit is fitted with an effective pressure sensor for this purpose. The effective pressure is converted into a voltage signal by an effective pressure transducer with a dynamic measurement principle. The volume flow rate actual value is available as a voltage signal and digital information. The factory setting is such that 10 V DC always corresponds to the nominal flow rate (qvnom). Voltage ranges are stored in the transducer. 


1 Type

VMR Volume flow rate measuring unit

3 Material

Galvanised sheet steel (standard construction)

P1 Powder-coated RAL 7001, silver grey

A2 Stainless steel construction

5 Nominal size [mm]

100, 125, 160, 200, 250, 315, 400

7 Attachments (effective pressure transducer)

BTD Effective pressure transducer for measuring units, dynamic

9 Signal voltage range

0 0 – 10 V DC

2 2 – 10 V DC


Variants

  • VARIANTS


Product details, Technical data

  • PRODUCT DETAILS

Analogue interface 0 – 10 V DC or 2 – 10 V DC

The analogue interface can be set for signal voltage range 0 – 10 V DC or 2 – 10 V DC. The assignment of actual flow rates to voltage signals is shown in the characteristic curves.

  • The signal voltage range is set in the factory according to the order code
  • The signal voltage range can be adjusted by others using the TROX FlowCheck App or PC-Tool

If the digital communication interface is used, the output channel can be changed to Modbus, BACnet or MP bus at any time via the TROX FlowCheck app.

Actual value as feedback for monitoring or tracking control

  • The actual volume flow rate measured by the controller can be picked up as a voltage signal at terminal 5
  • The selected signal voltage range 0 – 10 V DC or 2 – 10 V DC is mapped on the volume flow rate range 0 – qvNom
  • In analogue mode, there is the parallel option of querying operating data via the digital communication interface (hybrid mode)

Digital communication interface

To use the digital communication interface, a change by others using the TROX FlowCheck app is required. The bus interface can be set to Modbus, BACnet or MP bus. For a smooth exchange of data in the bus network provided by others, the communication parameters and the user address for the bus interface are required. The communication parameters of the bus systems (address, baud rate, etc.) can be set using the TROX FlowCheck app. The Modbus and BACnet interfaces provide standardised bus register/object access to the available data points. Additional hardware and software from official MP bus partners is required for further processing of the MP bus data.

Actual value as feedback for monitoring or tracking control

  • The actual values can be read out in m³/h in both the Modbus and BACnet (factory setting). Other units such as l/s and cfm are possible
  • The volume flow rate actual value can also be read out as a relative percentage value via additional data points. 0 – 100 % is mapped on the volume flow rate range 0-qvNom
  • In addition to the actual value of the volume flow rate, further information on the other Modbus registers/BACnet objects can be read out as well
  • Overview of the registers/objects in the communication tables
  • For diagnostic purposes, the actual value of the volume flow rate can be picked up at terminal 5 in bus mode
  • The volume flow rate range 0 – qvNom always corresponds to the signal voltage range of (0)2 – 10 V DC

Downloads

Product informatie

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"0", "x-content-type-options"=>"nosniff", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8", "link"=>"</assets/application-fc43fee91a3a5a20a1d3533b2baaef10e978cba5ead1ed820f5d052821bf105a.css>; rel=preload; as=style; nopush,</assets/print-fec2e47d6d8dcc5d4c101139f17046ba981ca1c12f71e7e403fba50cc7584175.css>; rel=preload; as=style; nopush,</assets/other_js/js.cookie.min-2d7f0947351ac6299750bed81152f833ef9f445001eb6cbaf4b88a0599dd3b84.js>; rel=preload; as=script; nopush,</assets/other_js/jquery-3.5.1-2c4ce18a1a3f144c333912efc24a76c9a165a0dba9f88a499985df1af0a196a2.js>; rel=preload; as=script; nopush"}

Deel deze pagina

Beveel deze pagina aan

U kunt deze pagina delen door de link te delen.

Velden met een ster (*) zijn verplichte velden.

Contact

Bedankt voor uw bericht!

Uw aanbeveling is verzonden naar de ontvanger.

Contact

Wij zijn er om u te helpen.

Geef alstublieft het onderwerp van uw vraag en uw contactgegevens.
Tel.: +31(0)183 767300 | Fax: +31(0)183 767399

Attachment (max. 10MB)

Velden met een ster (*) zijn verplichte velden.

Contact

Bedankt voor uw bericht!

Uw bericht is ontvangen door ons Service Center en wordt verwerkt.
Onze service-afdeling neemt contact met u op.
Als u algemene vragen over onze producten en services heeft, kunt u ons ook bereiken op:
Tel.: +31(0)183 767300 | Fax: +31(0)183 767399

Contact

Wij zijn er om u te helpen.

Geef alstublieft het onderwerp van uw vraag en uw contactgegevens.
Tel.: +31(0)183 767300 | Fax: +31(0)183 767399

Attachment (max. 10MB)

Velden met een ster (*) zijn verplichte velden.

Contact

Bedankt voor uw bericht!

Uw bericht is ontvangen door ons Service Center en wordt verwerkt.
Onze service-afdeling neemt contact met u op.
Als u algemene vragen over onze producten en services heeft, kunt u ons ook bereiken op:
Tel.: +31(0)183 767300 | Fax: +31(0)183 767399